Globecore Breakdown voltage tester TOR-80
Page view:
Globecore Breakdown voltage tester TOR-80
编号
描述
Application
- The unit is designed to determine the electrical breakdown voltage of transformer oil and other liquid dielectrics.
- It is a fully automatic device that provides testing according to the procedures defined by these standards, as well as according to the user procedures specified in the corresponding section of the installation menu.
Technical specifications
Parameter
|
Value
|
Operating voltage AC, V
|
85…264
|
Power consumption, max. VA
|
250
|
Maximum output voltage, kV
|
Sinusoidal, up to 80kV
|
Output voltage measurement
precision
|
1 %
|
Voltage rate of rise, kV/s
|
from 0,1 to 5 (variable )
|
Resolution when displaying the
output voltage, V
|
100
|
High voltage shutdown time after breakdown, μs
|
10 max, 4 typical
|