Search

PRODUCTS

图片名称
+
  • INDUBRAS Sudden Pressure Relay.png

INDUBRAS Sudden Pressure Relay


Description

Sudden pressure relays with contacts for sealing transformers

Specification

Sudden pressure relays with contacts

Application

For sealing transformer

parameters

Pressure relay


Feature

Sudden pressure


  • Description
  • Type parameter
    • Commodity name: INDUBRAS Sudden Pressure Relay
    • Commodity ID: 1105555519721590784
    • 规格1: Sudden pressure relays with contacts
    • 应用: For sealing transformer
    • 类型: Pressure relay
    • 特征: Sudden pressure

    Sudden pressure relays with contacts for sealing transformers

    SUDDEN PRESSURE RELAY WITH CONTACT, FOR SEALED TRANSFORMERS
    MODEL: RPS-114.A
    • BODY AND COVER: aluminum.
    • TERMINALS: brass/ nylon — M5 Thread.
    • FIXING ELEMENTS: stainless steel.
    • GASKETS: nitrile rubber (DIN 3771).
    • INSULATION: 1.5kV 60Hz in 1 minute.
    • PAINT: gray epoxy Munsell notation N.6,5.
    • PROTECTION RATING: IP-66, as per NBR IEC 60529.
    • TIGHTNESS: at a 2kgf/cm2 (28.4psi)  pressure, at 110°C (230°F).
    • NUMBER OF OPERATIONS: higher than or equal to 10,000.
    • MINIMUM CONTACT ACTUATION PRESSURE: 0.03Kgf/cm2 (0.43psi) .
    • MAXIMUM PRESSURE FOR CONTACT ReTURninG TO iTS ReST POSiTiOn:0.02kgf/cm2 (0.28psi).
    • ELECTRICAL CONTACTS CHARACTERISTICS:
      – conduct: 0.5A at 125VDC and 6.0A at 220VAC;
      – interrupt: 0.5A at 125VDC and 6.0A at 220VAC
    • DIMENSIONS: millimeter.
       
       
       

       
  • MODEL: RPS-114.A
    • BODY AND COVER: aluminum.
    • TERMINALS: brass/ nylon — M5 Thread.
    • FIXING ELEMENTS: stainless steel.
    • GASKETS: nitrile rubber (DIN 3771).
    • INSULATION: 1.5kV 60Hz in 1 minute.
    • PAINT: gray epoxy Munsell notation N.6,5.
    • PROTECTION RATING: IP-66, as per NBR IEC 60529.
    • TIGHTNESS: at a 2kgf/cm2 (28.4psi)  pressure, at 110°C (230°F).
    • NUMBER OF OPERATIONS: higher than or equal to 10,000.
    • MINIMUM CONTACT ACTUATION PRESSURE: 0.03Kgf/cm2 (0.43psi) .
    • MAXIMUM PRESSURE FOR CONTACT ReTURninG TO iTS ReST POSiTiOn:0.02kgf/cm2 (0.28psi).
    • ELECTRICAL CONTACTS CHARACTERISTICS:
      – conduct: 0.5A at 125VDC and 6.0A at 220VAC;
      – interrupt: 0.5A at 125VDC and 6.0A at 220VAC
    • DIMENSIONS: millimeter.